Air Changes per Hour Calculator
Calculate the air changes per hour a given airflow delivers in a room, and the CFM needed to hit a target ACH.
Loading calculator…
What this tool does
Calculate the air changes per hour a given airflow delivers in a room, and the CFM needed to hit a target ACH. Room is treated as a rectangular box. Enter outdoor airflow if you want fresh-air changes rather than recirculation.
How to use the Air Changes per Hour Calculator
- Enter or select airflow (cfm).
- Enter or select room length in ft.
- Enter or select room width in ft.
- Enter or select room height in ft.
- Enter or select target air changes per hour.
- Read the calculated result; change any measurement to compare alternatives.
Formula
ACH = CFM × 60 ÷ (length × width × height); required CFM = target ACH × volume ÷ 60
- cfm
- Airflow (CFM)
- length
- Room length (ft, before metric conversion)
- width
- Room width (ft, before metric conversion)
- height
- Room height (ft, before metric conversion)
- targetAch
- Target air changes per hour
Room is treated as a rectangular box. Enter outdoor airflow if you want fresh-air changes rather than recirculation.
Worked example
For air changes per hour calculator, the following measurements illustrate the exact method: Airflow (CFM): 500; Room length: 20; Room width: 15; Room height: 8; Target air changes per hour: 6.
Inputs
- Airflow (CFM)500
- Room length20 ft
- Room width15 ft
- Room height8 ft
- Target air changes per hour6
Result
- Air changes per hour (ACH)12.5
- Room volume (cu ft)2,400
- CFM needed for target ACH240
Results explained
- Air changes per hour (ACH)
- Air changes per hour (ACH) from the formula above. Room is treated as a rectangular box. Enter outdoor airflow if you want fresh-air changes rather than recirculation.
- Room volume (cu ft)
- Room volume (cu ft) from the formula above. Room is treated as a rectangular box. Enter outdoor airflow if you want fresh-air changes rather than recirculation.
- CFM needed for target ACH
- CFM needed for target ACH from the formula above. Room is treated as a rectangular box. Enter outdoor airflow if you want fresh-air changes rather than recirculation.
Frequently asked questions
ACH = airflow (CFM) × 60 ÷ room volume (ft³). A 500 CFM fan in a 20 × 15 × 8 ft room (2,400 ft³) gives 500 × 60 ÷ 2,400 = 12.5 air changes per hour.
Common design targets: bedrooms and offices about 4–6, kitchens and bathrooms higher with local exhaust, and healthcare or lab spaces set by code. Treat these as orientation — local ventilation codes govern.
They are the same equation rearranged. The CFM tool starts from a target ACH and returns airflow; this one starts from an airflow and returns the ACH it achieves, plus the CFM a target ACH would need.
Only if the airflow is outdoor air. Recirculated air through a filter changes air movement but not fresh-air ACH; enter the outdoor-air portion of the flow for ventilation ACH.
The room's air volume: length × width × ceiling height. Sloped ceilings and large fixed furniture make this an approximation.